….let's share our railways knowledge

Overhead Equipment – Overlaps

By on March 29, 2014

In electrical circuit, the series and parallel connections are made using junction box, twisted of cables together, soldering, brazing, etc.

This is not possible in case of overhead contact and catenary wire. Similar purpose in OHE is achieved  through overlaps. Overlap is defined as an arrangement where two set of contact wire runs together in parallel for a short distance without any mechanical or electrical connectivity but facilitating smooth movement of pantograph over it. The two contact wires are either connected firmly by a jumper or an isolator/ interrupter. It is called un-insulated overlap when connected firmly and insulated when connected through a switch like isolator or interrupter.  The need for the overlaps arises because of

  1. Restriction on the length of the conductor due to handling of weight, drum size, tension to restrict the sag and elongation due to temperature variation depends on length.
  2. Maintenance management of higher length is difficult for schedule replacement, kink attention etc.
  3. Separate tension length of loop line, yard lines, loco maintenance lines, etc.
  4. Segregation of section to minimize the faulty section to minimize the impact of fault on the running of trains.

 Un-insulated OverlapUn-insulated Overlap

Un-insulated overlap is required when continuity of current flow is required between two conductors whose length is limited due to design considerations. The contact wire cannot be indefinitely long and a standard length of 1.6 Km is designed taking into consideration the thermal expansion, tension, weight, etc. This length is also called one tension length.

Two sets of conductors are separated by 200 mm & connected by a large jumper of 105 sq.mm. cross-section.

The overlap is either 3 or 4 span length. Three span length overlap is used when radius of curvature is more than 5000 m with span length more than 54 m and four spans with radius of curvature less than 5000 m with span length less than 54 m.

Un-insulated overlaps are provided for connectivity for two tensions lengths.

Insulated Overlaps

In Insulated Overlaps, the two sets of Conductors are separated by 500 mm in air. The gap is decided requiring  the minimum air clearance  for 25 kV. With this clearance, it is possible to make one length dead keeping the other energized by opening the switch that normally connects the two lines. The switch is either an isolator or interrupter. Isolator is operated manually where as interrupter by a command from remote center through SCADA. Insulated overlaps are preferred at the following locations

  1. At sub-sectioning and paralleling post (SSP) where  two tension lengths are connected by an interrupter.
  2. OHE is sub-divided into different elementary sections between two SSP to facilitate minimum OHE isolation during fault condition.
  3. Yard,  loop and maintenance lines
  4. Neutral Section

Section Isolator for Elementary sections at a Railway Station

Diagram below showing Section Isolator, Insulated and Un-insulated overlap at a Railway Station

Station Diagram

See the current collection

 http://youtu.be/WhN7E6DhAQU

 

 

 

 

 

 

 

 

 

Post a Reply to Mojakkir Mallick Cancel Comment

Your email address will not be published. Required fields are marked *

There Are 8 Comments

  1. mukesh kumar says:

    this diagram isvery helpinig of new trd staf

  2. BHAVANIPRASAD says:

    unisulated overlap

  3. Nivtral section ki jankari mast h.

  4. Mojakkir Mallick says:

    TRD
    All
    Work handbook
    Vej dia Sir ok

  5. CHANDAKA VENU GOPAL says:

    How many masts are there between OPEN DJ and CLOSE DJ boards in
    an overlapping natural section.

  6. Bhushan Wahane says:

    Can u published this ohe book as given by customers

  7. Yatin Rajput says:

    Sir I want to know about OHE foundation detail.

Top